Electric Power Leads


I have noticed that some folks coil up the Electric Power Leads, does this increase voltage to a point where it can cause damage any sensitive electrical equipment in the caravan?

What's your thoughts.



Attachments
__________________

Michael C

 



Guru

Status: Online
Posts: 4179
Date:

As long as there is good airflow, there shouldn't be a problem.

https://electronics.stackexchange.com/questions/192923/why-is-it-dangerous-use-a-coiled-extension-cord



__________________

"No friend ever served me, and no enemy ever wronged me, whom I have not repaid in full."

Lucius Cornelius Sulla - died 78 BC 

 



Senior Member

Status: Offline
Posts: 311
Date:

No voltage issue, but there is some heat developed with every electrical lead and if it is heavily loaded and coiled too tight that heat can become destructively high, melt the insulation and cause a fire.
Always uncoil extension leads when in use.
Cheers,
Peter

__________________

OKA196 DIY, self contained 4WD MH, 1160W PV, 326Ah of CALB LiFePO4 batteries, 1.3kW inv, 310L water, 350-450L diesel.



Guru

Status: Offline
Posts: 839
Date:

Damn good advice there. I always make sure the cable is uncoiled, especially when running the air conditioner on the Generator.

__________________

We acknowledge and pay our respects to the British and European Elders past and present, who introduced civil society and prosperity to Australia. 



Veteran Member

Status: Offline
Posts: 69
Date:

Yes, great advice.

Thanks

__________________

Michael C

 



Guru

Status: Offline
Posts: 4730
Date:

Steel Dog wrote:

I have noticed that some folks coil up the Electric Power Leads, does this increase voltage to a point where it can cause damage any sensitive electrical equipment in the caravan?


 As described above, any damage that occurred, occurs in the lead. The resistance in the lead causes a voltage drop along the length of the lead. If you multiply that voltage drop by the current flowing in the lead, you can calculate the power being lost in the lead and thus the heat generated in the lead. If you coil the lead tightly you prevent the heat escaping. This is what caused the insulation melting and the destruction of the lead.

The maximum current rating of a lead is based upon a maximum of 5% voltage at the socket end of the lead. With our 230 V system this equates to 11.5 V drop through a lead at its maximum allowable length for a given size of cable at 16 A. If you have a 25-metre lead and yuou are using your maximum allowable power, you will be losing 184 W of power in your lead. That is not an insignificant loss of power and if you have your lead on a reel then you can destroy it in very quick time.



__________________

PeterD
Nissan Navara D23 diesel auto, Spaceland pop-top
Retired radio and electronics technician.
NSW Central Coast.

 



Guru

Status: Offline
Posts: 7579
Date:

Looking at HPM website.

 

Domestic extension lead 1mm²

Heavy duty lead 1mm²

Extra heavy duty lead 1.5mm²

Extra heavy duty caravan lead 1.5mm²

 

My Arri light extension lead 4.0mm²

 

If you want to minimise cable losses & reduce heat, get thicker cross sectional area of wire.



__________________

Procrastination, mankind's greatest labour saving device!

50L custom fuel rack 6x20W 100/20mppt 4x26Ah gel 28L super insulated fridge TPMS 3 ARB compressors heatsink fan cooled 4L tank aftercooler Air/water OCD cleaning 4 stage car acoustic insulation.

Page 1 of 1  sorted by
 
Quick Reply

Please log in to post quick replies.

Tweet this page Post to Digg Post to Del.icio.us
Purchase Grey Nomad bumper stickers Read our daily column, the Nomad News The Grey Nomad's Guidebook