Change panels from parallel to series


G'Day

I am going to install a new MPPT controller and the recommendation is to change from parallel  to series.

From the pwm picture the positive and negative leads from two panels  are wired into the same ports on the controller, to make it series do I join one +ve to -ve ( in an isolated block) and then wire the other +ve and -ve into the respective ports on the new controller?

Cheers

 



Attachments
__________________


Guru

Status: Offline
Posts: 1927
Date:

Hi 2Lazy smile

Yes you are correct about the wiring for series connection.

You do not have to do that however, you could just wire them up in parallel as you have done the other controller. There will be no difference in output IMHO in your case. I assume you have normal 12V panels with a VMP about 17-18V.

Cheers jaahn   



__________________


Member

Status: Offline
Posts: 7
Date:

Thanks, I was told more that a series connection would be more efficient as a higher voltage lower amperage would result in less loss in the cables and more amps to the batteries

If this is marginal, I will just replace like for like

Cheers

Les



__________________


Guru

Status: Offline
Posts: 3066
Date:

Marginal mate.
That's why 99.99% of 12\24v Solar systems are Parallel.
up to 340w myself.
Others having much more.

Don't ask for trouble for a marginal gain.

Something like moving a single panel round after max, sun.

It realistically, makes minimal difference for the time and effort taken.

Lot's have tried over the decades. lot's no longer bother.
It's easier to just add an extra panel.

__________________


Guru

Status: Offline
Posts: 1927
Date:

2Lazy wrote:

Thanks, I was told more that a series connection would be more efficient as a higher voltage lower amperage would result in less loss in the cables and more amps to the batteries

If this is marginal, I will just replace like for like

Cheers

Les


 Hi Les smile

What was said can be correct if the wires are connected in series close to the panels so the current is reduced in the wiring going down to the controller. But in your case they are just connected at the controller anyway so no difference in losses.

I assume your controller will be close to the battery as it should be. To get the most benefit from a MPPT controller the wiring size from the panels should be generous too.

Jaahn 

 



__________________


Member

Status: Offline
Posts: 7
Date:

Thanks

I have installed as a straight replacement, moving the  controller and changing cable rating and run are both a pain, I will see how the new set operates on a day to day basis before ripping cabling out of the van

 

Cheers

Les



__________________


Guru

Status: Offline
Posts: 4711
Date:

Les. Jaahn has explained that there will be no advantage in the way of power loss for series connection. There is also another thing to consider and that is panel shading. If you are running a series string, if one panel gets shaded your array will nearly close down. If you have the panels in parallel and one gets shaded, the other panel will still operate at full capacity. Your charging will thus be better with the parallel panels.



__________________

PeterD
Nissan Navara D23 diesel auto, Spaceland pop-top
Retired radio and electronics technician.
NSW Central Coast.

 



Senior Member

Status: Offline
Posts: 159
Date:

Series has a number of advantages that are discussed in detail by others elsewhere.

Series becomes important when you get to large arrays. We have 1410 W of panels and have gotten over 1400 W into controller when camped at 3.5 km, sunny days, in June.
This is 117 amps at 12 V but only 16 amps at 90 V and 29 amps at the 48 V nominal of the LFP battery suite. We have a 45 amp MTTP controller and thus have 50% over capability

Reed and Elaine

__________________


Senior Member

Status: Offline
Posts: 348
Date:

Hiya 2lazy,
be aware that if you "series" up the voltage past 49 you require a registered sparky for the fit........

__________________


Guru

Status: Offline
Posts: 7640
Date:

Short distance as in caravan etc there's not much gain ! In a house situation ? Distances can be longer so is the load and output. parallel can be multy cables to regulator .. Or run in groups .. We are running a low wattage system compared to home solar .. 400 watt is enough for most system with 2 or 3 batteries . Or should I say 2 or 300AH ... 50% more than required so there's less drain on batteries ..

__________________
Whats out there


Senior Member

Status: Offline
Posts: 353
Date:

hi
Everybodies got it nailed

Series is beneficial for
long cable runs ,
a little loss does not matter ,
miss matched panels work better in this situation Victron mentions this .

negs in semi shade u have a great reduction in power



www.victronenergy.com/blog/2015/11/10/connecting-different-sized-victron-energy-pv-modules-series-or-parallel/

www.youtube.com/watch [ actual reality no bs] proof in a small well designed system [same panels ] system ,series vs parallel makes little difference .

__________________


Member

Status: Offline
Posts: 7
Date:

All Thanks for the advice, wired in parallel and been off grid for 7 days. Batteries (2 x 120 AGM Deep cycle) go to float around lunch off 300 Watts of panel Cheers

__________________


Guru

Status: Offline
Posts: 3066
Date:

Hi.
OK so far. But a little light on with the panels when weather gets moody.
I'd stick another one up there. Just to be sure.